1Model 5000 Electronic Air CleanerInstallation InstructionsWARNING120 Volts may cause serious injury from electrical shock. Disconnect power to the fu
10RTHERMOSTATGYWCOOLINGHEATINGFANGSWGFCRAIR CLEANER CONTROLDISCONNECT EXISTING WIRE FROM THERMOSTAT G (FAN) TERMINAL AND USE WIRE NUT TO CONNECT TO GF
1190-1351RFURNACE OR AIR HANDLERCGYW1COOLING OR COMPRESSORL1L2120 VAC24 VACHEAT OR AUX. HEATFANGSWGFCRDISCONNECT EXISTING WIRE FROM FAN TERMINAL AND U
12LED BASEAIR CLEANER CONTROLGSWGFCRBAGSWGFCRBANOT USEDNOT USEDRFURNACE OR AIR HANDLERCGYW1COOLING OR COMPRESSORL1L2120 VAC24 VACHEAT OR AUX. HEATFANG
131. Restore power to the HVAC equipment.2. Set the thermostat mode to OFF and fan to AUTO.3. The display on the Air Cleaner Control should look li
14TROUBLESHOOTING GUIDEPROBLEM POSSIBLE CAUSE(S) SOLUTION(S)Light does not come on at all after 90 secondsON/OFF switch not in ON position Turn switch
15Inner HousingIonizer FrameControlElectrodeControl ElectrodeIonizer FrameControlElectrodeGroundContactMedia GroundContactsIonizerWiresBus BarFIGURE 2
16RESEARCH PRODUCTS CORPORATIONP.O. BOX 1467 • MADISON, WI 53701-1467 • PHONE: 800/334-6011 • FAX: 608/257-4357 • www.aprilairecontractor.com10007971
2FIGURE 1 – Dimensions of the Model 5000 Electronic Air Cleaner© Research Products Corporation 200831" with Door28-1/8" without Door12"
3Pleat Spacers (6)#501 MediaOuter Housingwith Door RetainersInner Housing AssemblyInnerHousingIonizer FrameControl ElectrodePower Pack/DoorAssemblyOn/
4LOCATING THE AIR CLEANERAirflow Airflow Airflow Airflow 30 max. 45 max. Minimize Angles Where PossibleAirflow Plenum Box Airflow Plenum Box Size Plen
5 1. Turn the system OFF at the thermostat by changing the mode selector to OFF – this may be a switch or a pushbutton, depending on the type of ther
6WIRING AND START UP 1. Install a grounded (earth ground) 120-volt single receptacle outlet in accordance with NEC Standards and local codes, into w
7EACNEUTRALGNDHVAC Equipment Control Center Circuit BoardIT IS COMMON TO SEE SPADE TERMINALS ON THE HVAC EQUIPMENT CONTROL CENTER CIRCUIT BOARD. USE
8The electronic controls that are included with the air cleaner are used to circulate air through the air cleaner, monitor filter life and inform the
91 Run a 3-conductor cable between the LED Base and the low voltage controls of the HVAC equipment.2 Remove the cover from the LED Base and wire t