Model 8100 Energy Recovery VentilatorInstallation InstructionsREAD AND SAVE THESE INSTRUCTIONS CAUTION1. Read all instructions before beginning insta
SYSTEM START-UPCONSTANT ON OPERATIONOPERATION WITH HOME COMFORT CONTROL™ (FIGURE 20)OPERATION WITH 8120 VENTILATION CONTROLLER OR THIRD-PARTY CONTROL
SYSTEM START-UP (CONTINUED)Table 2 – Ventilation Air Requirements, CFMHome Size (ft2)Number of Bedrooms< 2 2 - 3 4 - 5 6 - 7 > 7≤ 150030 45 60 7
P.O.Box1467•Madison,WI53701-1467•Phone:800/334-6011 •Fax:608/257-4357•www.aprilairepartners.com10009736 1.12B2701202APrinted in U.S.A.©
SPECIFICATIONSDimensionsUnit – 37-7/16” W x 12-3/4” D x 20-9/16” H EnergyMax Transfer Core – 12-1/8” x 12-1/8” x 10-3/4”Weight75 lbs.Performance77% Ap
SERVICECLEARANCE12"12"36"37-7/16"20-9/16"CEILING MOUNTING HOLESCEILING MOUNTING HOLESON / OFFSWITCHWALLMOUNTINGHOLESWALLMOUNT
The unit can be mounted on a concrete wall or on a stud wall. The mounting bracket is pre-drilled for fastening to standard 16” O.C. or 24” O.C. stud
MECHANICAL INSTALLATION (CONTINUED)CEILING MOUNT The unit can be mounted on ceiling joists. The mounting bracket is pre-drilled for fastening to stand
MECHANICAL INSTALLATION (CONTINUED)DUCTINGDUCT WORK SPECIFICATIONS•Planontemporarilyinstallingtwoairflowmeasuringdevices.Thesystemwillha
MECHANICAL INSTALLATION (CONTINUED)DUCTING (CONTINUED)RETURN: FROM LIVING SPACE TO ERV•Staleairfromthehouseshouldbeexhaustedfromoneexhaust
MECHANICAL INSTALLATION (CONTINUED)BALANCING THE SYSTEMDUCTING (CONTINUED)EQUIPMENT REQUIRED•Theintakeandexhausthoodsmustbelocatedatleast1
5 FT. MIN.5 FT. MIN.2-1/2 FT2-1/2 FTPRESSURE GAUGESSTALE AIRFROM HOUSEFRESH AIRFROM OUTSIDEFRESH AIRTO HOUSESTALE AIRTO OUTSIDEAIR FLOW MEASURINGDEVIC