STEP 12: Humidifier Wiring
Strip the wires used for all the Humidifier Control
terminal connections 1/4 inch.
If FURNACE ACCESSORY TERMINALS are used, wire the solenoid
valve in series with the “H” terminals on the Humidifier Control
without using a Model 50 Relay. See furnace manual for operation
of accessory terminals. (Figure H)
If an EXTERNAL TRANSFORMER is used, a Model 50 Current
Sensing Relay must be connected to the solenoid valve and the
“H” terminals on the Humidifier Control to allow the humidifier to
operate only when the blower is on. (Figure I)
Wire the Model 50 Relay into the “H” circuit only.
Bypass and Power units are wired to the AHC in the same fashion.
System Checkout
1. For system Test/Reset, be sure that 24 VAC is applied to the “R” and “C”
terminals of Humidifier Control.
2. Snap the door back onto the Humidifier Control Base.
3. Activate furnace blower and be sure thermostat is calling for heat.
4. Rotate the control knob of Humidifier Control clockwise to the “Test/Reset”
position. When the knob is set in the “Test/Reset” position, the green
“Change Water Panel” light will blink. Make sure the knob is not left in the
“Test/Reset” position when the installation is done. Rotating knob to test
position resets the water panel change timer to zero. The Control must be
energized to reset the Water Panel Indicator.
5. If all is set up properly, you should be able to hear the solenoid valve click
open. In “Test/Reset” mode, the Aprilaire Humidifier will operate for 1 minute.
6. If the humidifier does not activate with the Humidifier Control in
the “Test/Reset” position, refer to troubleshooting guide.
7. Setting the Humidifier Control:
If home is occupied, set Humidifier Control to “Normal”
(For Manual Operation, set to 35%)
If home is vacant, set Humidifier Control to “Off”
8. Inform homeowner to refer to the Aprilaire Owner’s Manual for the initial
adjustment period.
9. Make sure the Red Diagnostic Light is not lit. If the Red Diagnostic Light is
lit, re-check your wiring. If the Red Diagnostic Light does not go off, replace
the Humidifier Control with a new unit.
Humidifier Control Troubleshooting Guide
Applies to both Automatic and Manual Operation unless indicated otherwise.
SYMPTOM
Humidifier does not
operate in “Test” mode
TROUBLESHOOTING PROCEDURE
Make sure furnace blower is operating and thermostat is calling for heat.
Make sure the Outdoor Temperature Sensor is connected to the “ODT” terminals of the control. (For Manual Operation,
make sure Manual Mode Resistor Case is in place of the Sensor).
Check main wiring diagram for correct Humidifier Control installation.
If connected to a Model 400 Humidifier, make sure both floats in the bottom of the scale control insert are in the down
position. If necessary, dump out water to lower floats.
Check voltage at Humidifier Control “R” and “C” terminals. Voltage should be 22 VAC minimum – 30 VAC maximum.
Check Model 50 Current Sensing Relay (if used) for correct installation (see Model 50 instructions). Do not use Model 50
Relay in transformer circuit or “R” and “C” circuit of Humidifier Control. Model 50 relay is to be used in the “H” circuit only.
In “Test” mode, humidifier will operate for 1 minute only. DO NOT LEAVE IN TEST MODE AS HUMIDIFIER WILL NOT OPERATE
Make sure saddle valve is open.
WARNING
Sharp edges on the opening may cause cuts. Use care when cutting the plenum opening
and installing the Humidifier Control.
CAUTION
Do not mount Humidifier Control on supply plenum or duct. The unit will not withstand
supply temperatures and will malfunction!
When installing Humidifier Control on counterflow furnaces, ensure blower continues
to run after a heat call is satisfied to eliminate high temperatures from damaging the
Humidifier Control.
Do not mount Humidifier Control downstream of the bypass outlet. False humidity
conditions will cause humidifier to operate incorrectly.
1. TEAR OUT TEMPLATE ALONG PERFORATED EDGES.
2. PLACE THIS TEMPLATE ON THE RETURN PLENUM UPSTREAM OF (BEFORE) THE
HUMIDIFIER CONNECTION.
3. TRACE THE OUTSIDE EDGES OF THIS TEMPLATE.
4. REMOVE TEMPLATE AND ACCURATELY CUT THE PLENUM OPENING.
5. USING 4 SHEET METAL SCREWS, INSTALL HUMIDIFIER CONTROL IN PLENUM OPENING.
PERFORATED
HUMIDIFIER
CONTROL
TEMPLATE
FURNACE
ACCESSORY
TERMINALS
(10 VA MINIMUM)
Figure H
Furnace
Accessory
Terminal
TRANSFORMER
(10 VA MINIMUM)
FURNACE BLOWER
Figure I
Constant
Power with
External
Transformer
Call your installer to have your Water Panel changed, or visit your installer to purchase a
new Aprilaire Water Panel. Follow the instructions on the Water Panel box.
“Change Water Panel”
Indicator is lit.