Control Panel Wiring Diagrams
APRILAIRE MODEL 6202 AND 6203 CONTROL PANELS
WIRING DIAGRAM
R 24V (hot) Thermostat voltage
C 24V (com) T-stat (if required) &
damper voltage
W Heat (thermostats and equipment)
Y Cooling (thermostats and equipment)
G Fan (thermostats and equipment)
NC Normally closed damper output
NO Normally opened damper output
RH Heating transformer24V (hot)
RC Cooling transformer24V (hot)
24VAC Voltage source for control panel,
T-stats and dampers
CONTROL PANEL TERMINAL DESIGNATIONS
Single-stage furnace and air conditioner application.
Aprilaire Zoned Comfort Control Panel
Wiring Diagrams
ADDITIONAL INSTALLATION FEATURES
• 45 DEGREE ANGLED TERMINALS
• ENCLOSURE ACCOMMODATES WIRING FROM THE SIDE OR REAR
• WIRING DIAGRAM ON FRONT COVER
• AVAILABLE TERMINAL FOR 24 VOLT POWERED STATS
• COMPATIBLE WITH COMMON POWER-STEALING THERMOSTATS
RATED VOLTAGE 20 to 30 VAC
RATED CURRENT 3 amp
FUSE RATING 3 amp, slow blow fuse
MAXIMUM AMBIENT TEMPERATURE 140˚F
RH AND RC TERMINALS Independent heat and cool relays for
2 transformer systems
PLENUM SENSOR
HIGH LIMIT TEMPERATURE Selectable between 120˚F and 160˚F
PLENUM SENSOR
LOW LIMIT TEMPERATURE Selectable between 40˚F and 45˚F
PRODUCT SPECIFICATIONS
MAX. # OF
POWERED
REQUIRED VA DAMPERS
40 3 or Less
75 4 thru 6
40 per 3 Dampers 7 or more
TRANSFORMER REQUIREMENTS